Scaling Transforms

The ACNET scaling system is a two-stage pipeline that converts raw device integers to engineering units and back. PACSys provides a client-side implementation that mirrors the Java DPM scaling service.

Low-level feature - most users don't need this

It is recommended to use the official scaling service or avoid .RAW entirely. ACNET backends (DPM/HTTP, DPM/gRPC, DMQ) return already-scaled engineering values. The Scaler class is only needed when working with performance-critical loops (e.g., fast setting of ramp tables).

Overview

Every ACNET reading/setting property has two transform indices stored in the device database:

  • Primary transform (p_index) -- converts raw bytes to "primary units" (hardware-level)
  • Common transform (c_index) -- converts primary units to engineering units using device-specific constants (C1..C6)
flowchart LR
    A["Raw bytes<br/>(int)"] -->|"Primary<br/>transform"| B["Primary units<br/>(float)"]
    B -->|"Common<br/>transform"| C["Engineering units<br/>(float)"]
    C -->|"Inverse<br/>common"| B
    B -->|"Inverse<br/>primary"| A

The forward path (scale) is used for reading; the inverse path (unscale) is used for writing.


The Scaler Class

from pacsys import Scaler

# Direct construction
s = Scaler(p_index=2, c_index=2, constants=(100.0, 1.0, 0.0), input_len=2)
eng = s.scale(1000)        # raw int -> engineering units
raw = s.unscale(eng)       # engineering units -> raw int

Constructor

Scaler(p_index: int, c_index: int, constants: tuple[float, ...], input_len: int)
Parameter Description
p_index Primary transform index (0-84, even numbers)
c_index Common transform index (0-90, even numbers)
constants Common transform constants (C1..C6 from device database)
input_len Raw data width in bytes: 1, 2, or 4

Methods

Method Direction Description
scale(raw) raw -> engineering Full pipeline: primary then common transform
unscale(value) engineering -> raw Full inverse: inverse common then inverse primary
raw_to_primary(raw) raw -> primary First stage only
primary_to_common(p) primary -> engineering Second stage only
common_to_primary(v) engineering -> primary Inverse second stage
primary_to_raw(p) primary -> raw Inverse first stage

All methods accept int, float, or numpy.ndarray. Arrays are processed element-wise via np.vectorize.

From DevDB

The typical workflow retrieves scaling parameters from the device database:

import pacsys
from pacsys import Scaler

with pacsys.devdb(host="...") as db:
    info = db.get_device_info(["M:OUTTMP"])
    prop = info["M:OUTTMP"].reading  # PropertyInfo

    scaler = Scaler.from_property_info(prop, input_len=2)
    eng = scaler.scale(raw_int)

PropertyInfo carries the scaling parameters:

Field Type Description
p_index int Primary transform index
c_index int Common transform index
coeff tuple[float, ...] Common transform constants (C1..C6)
primary_units str or None Label for primary units
common_units str or None Label for engineering units

Primary Transforms

Primary transforms convert raw integer data to a floating-point "primary" value. Indexed by even numbers 0-84. The raw input is sign-extended based on input_len (1 byte = signed 8-bit, 2 bytes = signed 16-bit, 4 bytes = signed 32-bit).

Transform Table

Index Formula Description
0 x / 3200.0 10.24V D/A converter
2 x / 3276.8 10V D/A converter
4 x / 6553.6 5V D/A converter
6 x / 13107.2 2.5V D/A converter
8 x + 32768.0 091 timing modules
10 float(x) Identity (DEC word order)
12 x / 320.0 Temperature resistors
14 float(m) * 10^c 2323 timing modules (BCD-like bit fields)
16 intBitsToFloat(x) IEEE float, DEC word order
18 x * 0.0010406 Temperature resistors
20 float(x) (unsigned) Unsigned interpretation (adds 65536 or 256 if negative)
22 intBitsToFloat(wordSwap(x)) / 4.0 VAX/DEC float to IEEE
24 intBitsToFloat(wordSwap(x)) IEEE float, 68000 word order
26 (unsigned(x >> 8) & 0xFF) / 82.1865 - 0.310269935 Pbar TWTs (high byte)
28 wordSwap(x) 68000 longword (integer result)
30 (byte) x Low byte, signed
32 (byte)(x >> 8) High byte, signed
34 x & 0xFF Low byte, unsigned
36 (x >> 8) & 0xFF High byte, unsigned
38 (x & 0xFF) / 82.1865 - 0.310269935 Pbar TWTs (low byte)
40 x / 256.0 Temperature resistors
42 (x & 0xFFFF) / 6553.6 16-bit unipolar 10V DAC
44 7-digit BCD decode Extracts 7 BCD nibbles from 28 bits
46 unsigned_long(x) Unsigned 32-bit to double
48 intBitsToFloat(x) / 0.036 Temperature resistors, IEEE float
50 intBitsToFloat(x) clamped to [-10.24, 10.235] IEEE float with clamping
52 float(byteSwap(x)) Byte-swap word or longword
54 x * 0.0004882961516 + 4.0 PLC 4-20mA (2 bytes, positive)
56 (unsigned(x) - 32768.0) / 3276.8 Stepper motor controllers (2 bytes)
58 unsigned(x) / 256.0 Unsigned divide by 256
60 500.0 * intBitsToFloat(x) IEEE float * 500
62 x / 6400.0 16-bit unipolar 0-10.24V DAC
64 x / {128, 32768, 2147483648} Scaled to +/-1.0 (depends on byte length)
66 x / 3200.0 (positive only) Like index 0, enforces positive input
68 Alternate scaling Delegates to string-based display
70 x / 1000.0 Divide by 1000
72 (unsigned(x) - 32768.0) / 3200.0 Unsigned word, offset, scale (2 bytes)
74 x * 0.00064088 Allen-Bradley PLC 0-21mA (2 bytes)
76 unsigned(wordSwap(x)) Word-swapped unsigned 32-bit (4 bytes)
78 intBitsToFloat(x) clamped to [0.0, 5.0] IEEE float with 0-5V clamp
80 intBitsToFloat(x) clamped to [0.0, 10.0] IEEE float with 0-10V clamp
82 x / 409.5 12-bit unipolar 0-10V (2 bytes)
84 intBitsToFloat(byteReversal(x)) IEEE float, full byte reversal (4 bytes)

Notes

  • intBitsToFloat reinterprets a 32-bit integer as IEEE 754 float
  • wordSwap exchanges the upper and lower 16-bit words of a 32-bit value
  • byteSwap reverses all bytes (2 bytes: AB->BA, 4 bytes: ABCD->DCBA)
  • Index 68 is a marker for "alternate scaling" (string-based display types like hex, enum, timestamp) -- not a numerical transform

Common Transforms

Common transforms convert primary-unit values to engineering units using device-specific constants (C1..C6) stored in the database. Indexed by even numbers 0-90.

Transform Table

Index Formula Constants Description
0 X' = X 0 Identity
2 X' = (C1*X/C2) + C3 3 Linear with scale and offset
4 X' = (X - C1) / C2 2 Offset then scale
6 X' = C1*X / C2 2 Ratio scale
8 X' = C4 + (C1*X)/(C3 + C2*X) 4 Rational function
10 X' = C3 + C2/(C1*X) 3 Inverse proportional
12 X' = C5 + C4*X + C3*X^2 + C2*X^3 + C1*X^4 5 4th-degree polynomial
14 X' = exp(C5 + C4*X + C3*X^2 + C2*X^3 + C1*X^4) - C6 6 Exponential of 4th-degree polynomial
16 X' = C2*exp(-X/C1) + C4*exp(-X/C3) 4 Sum of two exponential decays
18 X' = C3*exp(C2*(X+C1)) + C6*exp(C5*(X+C4)) 6 Sum of two exponential growths
20 X' = log10(X) / (C1*log10(X) + C2)^2 + C3 3 Logarithmic rational
22 X' = C2 * 10^(X/C1) 2 Power-of-10 scale
24 If X < C1: C2*(C3*X + C4); else: C2*exp(C5*X + C6) 6 Piecewise linear/exponential
26 X' = C6 + C5*X + C4*X^2 + C3*X^3 + C2*X^4 + C1*X^5 6 5th-degree polynomial
28 X' = C3/(C2 + C1*X) + C4 4 Inverse linear with offset
30 If X < C1: C6; else: C5 + C4*X + C3*X^2 + C2*X^3 6 Piecewise constant/cubic
32 X' = C2*ln(C1*X + C4) + C3 4 Natural logarithm
34 X' = (C2 + C1*X) / (C4 + C3*X) 4 Rational linear
36 X' = C2*sqrt(X + C1) + C3 3 Square root
38 If X > C6: 10^(C1 + C2*X + C3*exp(X) + C4/X + C5/X^2); else: 760000.0 6 Vapor pressure (C3=0 skips exp term)
40 X' = (C1*X/C2) + C3 6 Same as #2 (C4=min, C5=max, C6=knob step)
42 If X < C1: C2*X^2 + C3*X + C4; else: C2*exp(C5*X + C6) 6 Piecewise quadratic/exponential
44 If X < C1: C2*exp(C3*X); else: C4*exp(C5*X) 5 Piecewise exponential
46 If X < C1: C2*exp(C3*X^2 + C4*X); else: C5*exp(C6*X) 6 Piecewise gaussian/exponential
48 X' = C1 * C2^(1/X) * X^C3 3 Power/exponential composite
50 X' = C1 * acos(X/C2) 2 Arc-cosine
52 If X < C1: exp(C2*X + C3); else: exp(C4*X + C5) 5 Piecewise exponential
54 If X < C1: exp(C2*X^2 + C3*X + C4); else: exp(C5*X + C6) 6 Piecewise gaussian/exponential
56 Table lookup, linear interpolation 3 Not supported (requires DB tables)
58 Table lookup, exponential interpolation 3 Not supported (requires DB tables)
62 X' = C2 * (C3 + 10^(X/C1)) 3 Power-of-10 with additive constant
64 Hardcoded vapor pressure curves 1 C1=0 for N2, C1=1 for He
66 X' = C1 * 2^(C2*(X+C3)) + C4 4 Power-of-2 exponential
68 X' = C6 * (C2*ln(C1*X + C4) + C3*X)^C5 6 Log-power composite
70 X' = C1*exp(-X/C2) + C3*exp(-X/C4) + C5*exp(-X/C6) + 4 6 Triple exponential decay + 4
72 X' = C1 * 10^(C2 + C3*log10(X) + C4*log10(X)^2 + C5*log10(X)^3) + C6 6 Log-polynomial power
74 X' = (C1 + C2*X + C3*X^2) / (C4 + C5*X + C6*X^2) 6 Rational quadratic (Pade)
76 If X < C1: C2*X^C3; else: C4*exp(C5*X + C6) 6 Piecewise power/exponential
78 X' = C1 * 10^(C2*X + C3) + C4 4 Power-of-10 linear
80 X' = X 0 Identity (second)
82 X' = C2*log10(C1*X + C4) + C3 4 Base-10 logarithm
86 If X < C1: C3*X + C4; if X > C2: exp(C5*X + C6); between: log interpolation 6 Piecewise linear/log-interpolated/exponential
88 X' = (C1 + C2*X + C3*X^2) / (1 + C4*X + C5*X^2 + C6*X^3) 6 Pade approximant
90 Multifunction (range-based dispatch) 3 Not supported (requires DB tables)

Polynomial evaluation

Polynomial transforms (12, 14, 26, and the multifunction sub-transform 201) use Horner's method for numerical stability:

C5 + C4*X + C3*X^2 + C2*X^3 + C1*X^4
= C5 + X*(C4 + X*(C3 + X*(C2 + X*C1)))

Piecewise transforms

Many common transforms are piecewise - they use C1 as a threshold to select between two branches. This handles sensors with different characteristics in different operating regions (e.g., linear at low values, exponential at high values).


Inverse Transforms

Both primary and common transforms support an inverse path for writing raw values from engineering units.

Analytical inverses

Many transforms have direct algebraic inverses:

  • Linear (c2, c4, c6, c40): Direct formula inversion
  • Rational (c8, c10, c28, c34): Algebraic with divide-by-zero checks
  • Logarithmic (c32): exp((X' - C3) / C2) / C1 - C4/C1
  • Square root (c36): ((X' - C3) / C2)^2 - C1
  • Arc-cosine (c50): C2 * cos(X' / C1)

For non-invertible transforms (most exponential and polynomial cases), the inverse is computed numerically using a two-phase binary search:

  1. Interval finding - starting from the midpoint of the primary-unit range, expand outward to find an interval that brackets the target value
  2. Bisection - refine to tolerance uprlim / 131072 (capped at 0.0001), max 1000 iterations

The search bounds (lowlim, uprlim) are per-primary-transform constants defined in the Java source. A separate bisection method (max 30 iterations) handles the vapor pressure transform (c38).


Unsupported Transforms

Three common transform categories require server-side database tables and are not available for client-side scaling:

Index Type Why unsupported
56 Interpolation table (linear) Requires accdb.scaling_interpolation_table_values
58 Interpolation table (exponential) Requires accdb.scaling_interpolation_table_values
90 Multifunction (range dispatch) Requires accdb.scaling_multifunction_transforms

These raise ScalingError. Devices using these transforms must rely on server-side scaling (i.e., read the normal property or use DPM scaling service).


Error Handling

from pacsys import Scaler, ScalingError

s = Scaler(p_index=2, c_index=56, constants=(1.0, 0.0, 100.0), input_len=2)

try:
    s.scale(1000)
except ScalingError as e:
    print(e)  # "Requires interpolation table data..."

ScalingError is raised for:

  • Unsupported transform indices (56, 58, 90)
  • Unknown/invalid transform indices
  • Overflow during inverse transforms (value doesn't fit in target byte width)

numpy Support

Scaler accepts numpy arrays for batch conversion. numpy is an optional dependency - Scaler works without it for scalar values.

import numpy as np
from pacsys import Scaler

s = Scaler(p_index=2, c_index=2, constants=(100.0, 1.0, 0.0), input_len=2)

raw = np.array([1000, 2000, 3000, 4000])
eng = s.scale(raw)      # array of engineering values
back = s.unscale(eng)   # array of raw integers

Scaling for Different Properties

Scaling also applies to parts of other properties.

Property Scaling Type Details
READING Primary + Common Standard two-stage pipeline
SETTING Primary + Common Same pipeline, different p_index/c_index/constants
STATUS [NO SCALING] Per-device bit masks, not numerical scaling
CONTROL [NO SCALING] Maps operation names to raw values
ANALOG alarm Primary + Common 20-byte structure with tolerance values scaled through Primary+Common
DIGITAL alarm [NO SCALING] 20-byte structure with nominal/mask values

Historical Notes

The scaling system dates back to the early 1980s PDP-11 era. The original API was a set of FORTRAN functions with names built from a two-letter convention - PD prefix, then source/target unit codes:

FORTRAN routine Direction PACSys equivalent
PDUDCU Unprocessed Data -> Common Units Scaler.scale()
PDCUUD Common Units -> Unprocessed Data Scaler.unscale()
PDUDPU Unprocessed Data -> Primary Units Scaler.raw_to_primary()
PDPUCU Primary Units -> Common Units Scaler.primary_to_common()
PDCUPU Common Units -> Primary Units Scaler.common_to_primary()
PDPUUD Primary Units -> Unprocessed Data Scaler.primary_to_raw()

Scaling parameters were (are?) stored in a Process Data Block (PDB) -- a variable-length byte structure fetched from the system database. The PDB contained the primary transform index, common transform index, six constants, unit labels, and flags. This maps directly to PropertyInfo dataclass and parts of the new gRPC protocol. More than 50 years of data structure vintage!

Two primary transforms have evolved since the PDP-11 era:

  • p22 was originally a null transform ("X = input") because DEC/VAX floating point was the native format. When the system moved to IEEE 754, this became a DEC-to-IEEE conversion (word-swap + divide by 4).
  • p28 was a null transform for Motorola 68000 longwords. Modern little-endian systems need a word-swap to interpret the big-endian 68000 format.

Basic status originally defined 4 attributes (ON, READY, REMOTE, POSITIVE). A 5th attribute (RAMP) was added later.